Re: Fire protection in ISPs and collocation facilities

  • From: Mauro Lollo
  • Date: Mon Nov 06 12:42:27 2000


In my experience, I belive I'd agree with the USAF statement. In any fires that I've seen in or around data centre facilities, it has usually started outside of the actual equipment itself, with ancillary systems and other materials. (this has been mostly in enterprise settings, as opposed to ISP / Co-lo)

I've just about completed a new facility with both FM200 gas (above & below floor) and pre-action (dry-pipe) water with misting heads as a secondary. My biggest fire hazard concern is the electrical system and
electrical/communications cabling within the facility. We've probably all seen the bad practice of storing combustible materials within the
environment itself (paper manuals, boxes, etc).

I've also developed a great amount of respect for compressed gas
extinguishing systems (FM200, etc.). About three years ago I saw the
aftermath of a service person refilling a cylinder, when the neck of the valve broke. The 600lb cylinder went off like a torpedo (kind of like letting go of a ballon).....broke loose of its mounting an took off through the room, ramming several cabinets and blasting through floor tiles. The guy servicing it (the only person in the room at the time) actually survived, the cylinder brushed him as it took off and dislocated his arm. The data centre looked like a war zone when I walked into it....the force of the thing was incredible.


M.




From: Sean Donelan <[email protected]>
To: [email protected]
Subject: Fire protection in ISPs and collocation facilities
Date: 3 Nov 2000 01:39:18 -0800


What has been the fire experience for ISPs and collocation facilities?
Other than the infamous Ascend incidents, I don't recall any ISP or
collocation fire incidents during the last five years.

Why am I asking, because some code officials seem to feel the need
to develop a special code to cover collocation facilities popping
up all over the place.  But I think most collocation facilities are
generally constructed to exceed the current codes anyway, and are
generally much lower risk than the "normal" occupancies around them.

The US Air Force is revising its design guidance for fire protection
of computer-electronic equipment installations this year. In the most
recent draft, the USAF has ultra sensitive air sampling smoke detection,
wet-pipe automatic sprinklers and smoke exhaust systems in its design
guidance.

Based on a five year study, the USAF found the most significant fire
and smoke threats have originated outside the computer-electronic
equipment room.  Two-thirds of the fires originate outside the
computer-electronic room.

One-third of the fires originated within the vicinity of the computer-
electronic equipment. Less than 25% of the fires originate within the
computer-electronic equipment.

The single largest threat of fire to computer-electronic equipment is
the electrical distribution system.  Two-thirds of the dollar losses
(1/3 of the fires) are caused by fixed wiring, transformers, power
switching gear, light fixtures and extension cords.

In over 50% of the fires, the first material ignited is some type of
plastic, including electrical insulation.